Conductor: Stranded Copper Conductor
Insulation: Cross Link Polyethylene (XLPE)
Insulation Color: Plain copper wire covered
Temperature Range: -15℃ to +90℃
Nominal Voltage: 600V / 1000V
Voltage Rating | 600V / 1000V |
Temperature Limits | -15℃ to +90℃ |
Minimum Bending Radius | As per cable manufacturer datasheet |
Installation Environment | Should not be installed at temperatures below 0℃ or above 60℃ |
CCC CODE | CONDUCTOR SIZE | STRANDING | WEIGHT | OVERALL DIAMETER | GLAND SIZE |
mm² | mm² | kg/km | mm | ||
4 SPLITCON | 4 | 7/0.85 | 206 | 9.6 | 205 |
6 SPLITCON | 6 | 7/1.04 | 281 | 11.4 | 20 |
10 SPLITCON | 10 | 7/1.35 | 394 | 11.4 | 20 |
16 SPLITCON | 16 | 7/1.70 | 583 | 14.6 | 25 |
25 SPLITCON | 25 | 7/2.14 | 843 | 18.7 | 32 |
35 SPLITCON | 35 | 7/2.52 | 1300 | 23 | 40 |
NOMINAL CROSS SECTIONAL AREA (MM² ) | CLIPPED DIRECT AMPS | IN CONDUIT ON WALL AMPS | IN AIR AMPS |
4 | 41 | 37 | 42 |
6 | 50 | 46 | 51 |
10 | 68 | 63 | 70 |
16 | 99 | 88 | 100 |
25 | 130 | 117 | 135 |
35 | 120 | 110 | 129 |
NOMINAL CROSS SECTIONAL AREA (MM2 ) | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C – PHASE OHMS/KM | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C – NEUTRAL OHMS/KM | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C – EARTH OHMS/KM |
4 | 4.61 | 4 | 4.80 |
6 | 3.08 | 3.15 | 3.15 |
10 | 1.83 | 1.90 | 1.90 |
16 | 1.15 | 1.20 | 1.20 |
25 | 0.727 | 0.76 | 0.76 |
35 | 0.524 | 0.55 | 0.55 |